Spray polyurethane foam (SPF) roofing is sometimes considered as a lower-cost alternative to removing and replacing an ageing commercial flat roof. But what happens when the existing roofing system already has problems, and the new protective coating begins to deteriorate?
This real commercial roof observation involved a medium-sized shopping mall where a spray foam roofing system had been installed over an existing built-up roofing (BUR) system.
The owners had chosen the lower-cost approach rather than carrying out a more extensive roof replacement. Unfortunately, approximately three to four years later, they were experiencing widespread roof leaks.
The following photographs document what we observed and explain why the condition of an existing roof should never be overlooked when considering a new roofing system.
Watch the Video: Spray Foam Roof Failure After Just 3–4 Years
This video uses original photographs from the shopping mall roof observation to explain the visible deterioration, potential moisture concerns and the risks associated with roofing overlays.
What Did We Observe on the Shopping Mall Roof?
The roof displayed several concerning conditions, including deteriorating protective coatings, standing water, exposed underlying materials and problems around rooftop equipment.
These defects were not confined to one small area.
1. Widespread Spray Foam Roof Deterioration
The general roof photograph shows extensive surface discolouration and deterioration across the existing spray foam roofing system.
Areas of standing water were also visible.
Ponding water can increase exposure around existing defects and may indicate inadequate drainage or localised changes in roof levels.
However, standing water alone does not establish the cause of the reported leaks.
2. Deterioration Along the Roof Perimeter
At the roof perimeter, sections of the protective coating had deteriorated, leaving underlying materials exposed.
Roof perimeter details are particularly important because they form part of the waterproofing transition between the main roof surface and the building edge.
Where these details deteriorate, further investigation is needed to determine whether water can enter the roofing assembly.
3. Breakdown of the Protective Roof Coating
A spray polyurethane foam roof relies on a suitable protective coating to shield the underlying foam from ultraviolet exposure and weathering.
The photograph shows a localised area where that protective surface had broken down.
Once the coating becomes damaged, the exposed foam may deteriorate further, particularly if the condition is left unaddressed.
4. Extensive Coating Loss and Exposed Roofing Materials
In another area, the deterioration was considerably more extensive.
Large sections of the protective surface had been lost, exposing darker underlying roofing materials.
At this stage, simply applying another coating without first investigating the existing materials could leave underlying defects unresolved.
The depth of deterioration and condition of the concealed roof assembly would need to be established before selecting a suitable repair.
5. Grease Contamination Around Rooftop Kitchen Equipment
Another concern involved rooftop kitchen exhaust equipment.
The grease collection arrangement was not functioning correctly, and contamination was present around the surrounding roof area.
Depending on the roofing materials and protective coating involved, grease contamination can affect coating performance and complicate future repairs.
Rooftop equipment maintenance is therefore an important part of protecting a commercial roofing system.
6. Vegetation Growing Through the Roof Surface
Perhaps one of the most striking observations was vegetation growing directly through an opening in the roof surface.
Plant growth indicates a compromised area and raises concerns about moisture and the condition of the materials beneath.
However, vegetation alone does not confirm the extent of concealed moisture or establish whether the underlying insulation is saturated.
Further investigation would be required to determine the condition of the roof assembly.
Should Spray Foam Be Installed Over an Existing BUR Roof?
My professional recommendation is to be extremely cautious about installing spray polyurethane foam over an ageing built-up roofing system, particularly where moisture is already present within the existing roof assembly.
I would not recommend covering known wet insulation with another roofing system.
Adding a new waterproofing layer does not remove moisture trapped in the existing insulation or correct underlying deterioration.
Before considering any overlay, the existing roof should be assessed for moisture, insulation condition, drainage performance, structural suitability and compatibility with the proposed system.
Where insulation is wet or roofing materials have deteriorated extensively, removing and replacing the affected materials may be necessary.
Why Can a Lower-Cost Roofing Solution Become More Expensive?
The original owners of this shopping mall selected a lower-cost roofing approach.
Within approximately three to four years, they were experiencing widespread leaks and significant visible deterioration.
Although the photographs document multiple defects, they do not establish one single cause of the premature problems.
The important lesson is that the initial installation price should not be the only consideration.
The condition of the existing roof, suitability of the proposed system, installation quality, maintenance requirements and expected long-term performance all need to be considered.
A cheaper initial solution may ultimately become more expensive if the underlying roofing problems remain unresolved.
What Should Building Owners Do Before Considering a Roof Overlay?
Before installing a new roofing system over an existing commercial flat roof, building owners and property managers should establish:
- The type and condition of the existing roof assembly.
- Whether moisture is present within the insulation.
- Whether existing materials are suitable to remain in place.
- The condition of roof drains, perimeter details and penetrations.
- Whether rooftop equipment is contributing to deterioration.
- Whether the proposed roofing system is appropriate for the building.
Where concealed moisture is suspected, suitable investigation methods and verification may be needed before deciding on the scope of work.
The Lesson From This Real Roof Observation
This shopping mall demonstrates how several roofing problems can develop across the same roof.
Protective coating deterioration, exposed materials, grease contamination, vegetation growth and reported widespread leaks all contributed to concerns about the condition of the existing spray foam roofing system.
The correct response is not necessarily to apply another coating.
It is to understand the existing roof condition first, then determine whether targeted repairs, more extensive remedial work or full replacement is appropriate.
Concerned About Your Commercial Flat Roof?
If you’re responsible for a commercial building in British Columbia and have concerns about roof deterioration, recurring leaks or an ageing roofing system, Flat Roofing Insights can help you understand the available options.
Contact us to enquire about a commercial roof observation report.
Explore more real examples on our Flat Roof Problems page.